KNX 12 channels 10A switch control module

• Through the normally open contacts, 12 loads can be switched independently;
• The connection of the bus is completed through a bus connection terminal, no data rail data strip is required;
  • KNX software function: can be used as a normally closed contact or a normally open contact;
Each channel has a delay function;
Programmable setting feedback function.

technical parameter 
• Rated voltage: 230V AC, 50/60Hz
  • Rated current: 10A
• Module width: 6 modules = about 106mm
  • Installation method: 35mm standard DIN rail type
  • Load type: halogen lamp: 230V AC, maximum 1700W
Incandescent lamp: 230V AC, maximum 2000W
Fluorescent lamp: 230V AC, maximum 1800W
Capacitive load: 230V AC, 10A

Back to previous page